Toho-electronics TTM-509 Manuel d'utilisateur Page 48

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 66
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 47
TOHO TOHO ELECTRONICS INC.
DWG. No.
45-4199-E
PAGE
48/66
Character
PV screen
Auxiliary screen
Designation Description Initial value
38

ch

Set a control
sensitivity for the
main output
Thermocouple input
Setting range: 0 to 999 or 0.0 to 999.9
Setting unit: °C

40

ch

Set a control
sensitivity for the
auxiliary output
Resistance bulb input
Setting range: 0 to 999 or 0.0 to 999.9 or 0.00 to
999.99
(when the input type is

,

,
or

)
Setting unit: °C
Current and voltage inputs
Setting range: 0 to 99999
The decimal place can be set to a
desired position.
Setting unit: digit
* The differential gap (sensitivity) of the potentiometer
is set with the dead band.

39

ch

Position the OFF
point of the main
output
Thermocouple input
Setting range: -199 to 999 or -199.9 to 999.9
Setting unit: °C

41

ch

Position the OFF
point of the
auxiliary output
Resistance bulb input
Setting range: -199 to 999 or -199.9 to 999.9 or
-199.99 to 999.99
(when the input type is

,

,
or

)
Setting unit: °C
Current and voltage inputs
Setting range: -19999 to 99999
The decimal place can be set to a
desired position.
Setting unit: digit
