8. Connections
Host Computer
(Master Station)
Unit1
(Slave Station
Unit2
(Slave Station
Unit3
(Slave Station
A(+)
B(-)
A(+)
B(-)
A(+)
B(-)
A(+)
B(-)
terminating
resistor
terminatin
g resistor
Cable①
Cable②
Cable③
Above drawing shows example of connecting 1 to 3 slave stations to a master station.
Use cables with the same characteristic impedance for cables to .
- For slave station nos. 1 to 3, connect them dependently as shown in the drawing.
The same characteristic impedance cables are used for the connections between
the slave stations.
Attach terminating resistor to both the master station side and the farthest ones among the
slave stations (no. 3).
Make sure to select terminating resistor in order that the [Characteristic Impedance from cables
to ] = [Resistance Value of ] = [Resistance Value of ]
- Furthermore, use characteristic impedance cable whose [Resistance Value of ] // [Resistance
Value of ] (parallel combination resistance value) becomes above 75-ohms.