48-7009-E 5-72
*1: Bank automatic switching function selection (bAF)
Set the bank automatic switching ON/OFF.
Setting range Initial value: 0 Bank automatic switching run OFF
0: Bank automatic switching run OFF
1: Bank automatic switching run ON
*2: Bank automatic switching source setting (bAS)
Select an input source. The bank is switched in accordance with the input of the source selected.
Setting range Initial value: 0 Select a SV value
0: Select a SV value {only local and remote (only option Y)}.
1: Select a ramp SV value
2: Select a PV value
Note When [bAF 1], the [SET 04 SV] value is selected for AT (auto tuning) regardless of the source
setting, which is used for bank auto switching.
If the zone threshold* setting (PM*) is set, a bank matching the SV value is selected based on the
result from AT (auto tuning). That is, a result from AT is reflected to the bank selected with a
threshold. As such, if a [P, I, d] value is desired to set for each temperature, perform AT (auto
tuning) after setting said value in the bank.
*3: Zone threshold* setting [PM 1 to PM 7]
A threshold is set for automatically switching a bank. Seven threshold values at most can be set
for eight banks.
Setting range: SLL to SLH Initial value: SLH
*4: Zone threshold switching sensitivity range setting (ASC)
A sensitivity range set in ASC is provided for each threshold [PM*] used for bank automatic
switching. (See the diagram below.) The sensitivity range is common to each threshold.
Setting range: During the temperature input 0 to 999 (0.0 to 999.9) (C) Initial value: 0
During analog input 0 to 9999 (digit)
Auto-Switching
Source
BANK0
BANK1
BANK2
BANK3
BANK4
BANK5
BANK6
BANK7
PM1
PM2
PM3
PM4
PM5
PM6
PM7
SLH
SLL
PM*
(*=1~7)
Magnified
Drawing
ASC
When
"increasing"
Auto-Switching
Source
When
"decreasing"
Outset of
BANK
switching
Outset of
BANK
switching
Auto-Switching
Source
The sensitivity range is effective if a remote SV or PV is selected for the bank automatic switching
source setting [bAS]. Other than this, the range is ineffective.
Note Condition on enabled ASC setting
When [bAS 2]
When SET 02 [LR 1, 2] with [bAS 0]
Note Condition on unable ASC setting
When [bAS 1]
When SET 02 [LR 0], even though [bAS 0]
PM*
(*=1-7)