Toho-electronics TTM200 Manuel d'utilisateur Page 194

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 264
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 193
48-7009-E 6-46
Ramp time setting
SEt04
CNt
Setting content
Initial value
57
RMP
Thermocouple/resistance temperature detector input
0.0 to 999.9 (C/minute)
0.0
Voltage/current input
0 to 9999 (digit/minute)
0
Set the ramp time.
A change of SV per minute is set when SV is changed.
The ramp control starts from the present PV.
<Start condition>
(1) At power-on
(2) SV change when bank being switched over
(3) When RDY being switched over to RUN
SV
* Settable at bank setting
The setting value changes from the
temperature at start of the operation to SV,
using the operating amount set for RMP.
SV
RMP
1 minute
Time
At start
Note Event output during ramp
The SV during ramp is equivalent to the SV for deviation upper/lower limit, deviation upper limit, deviation lower limit and
deviation range.
Take care that SV is not a final target value.
Note In the case of ramp setting (RMP = 0), the ramp function does not work.
Vue de la page 193
1 2 ... 189 190 191 192 193 194 195 196 197 198 199 ... 263 264

Commentaires sur ces manuels

Pas de commentaire