48-7009-E 6-46
■ Ramp time setting
Thermocouple/resistance temperature detector input
0.0 to 999.9 (C/minute)
Voltage/current input
0 to 9999 (digit/minute)
Set the ramp time.
A change of SV per minute is set when SV is changed.
The ramp control starts from the present PV.
<Start condition>
(1) At power-on
(2) SV change when bank being switched over
(3) When RDY being switched over to RUN
* Settable at bank setting
The setting value changes from the
temperature at start of the operation to SV,
using the operating amount set for RMP.
Note Event output during ramp
The SV during ramp is equivalent to the SV for deviation upper/lower limit, deviation upper limit, deviation lower limit and
deviation range.
Take care that SV is not a final target value.
Note In the case of ramp setting (RMP = 0), the ramp function does not work.