Toho-electronics TTM200 Manuel d'utilisateur Page 187

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 264
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 186
48-7009-E 6-39
Secondary control loop anomaly PV threshold
SEt04
CNt
Setting content
Initial value
47
tS2
Thermocouple/resistance temperature detector input
0.0 to 999.9 (°C)0 to 999 (°C)
0
Voltage/current input
0 to 9999 (digit)
Set the secondary control loop anomaly PV threshold .
The function is to detect an abnormality in the control loop.
When width of tS1 has PV from an SV , a judgment of the loop anomaly acts.
The real judgment in PS2 and LoP2.
For details, see sectionLoop abnormality function on pages 5-38 and 39.
Control loop
anomaly PV
threshold
2
SV
setting
value
(TS2
PV
When PV is out of the judgment
domain, the control loop anomaly is
not judged.
PV indicates present temperature.
Temperature threshold is a value
specified by [SV TS2].
Judgment
domain
Non-
judgment
domain
Vue de la page 186
1 2 ... 182 183 184 185 186 187 188 189 190 191 192 ... 263 264

Commentaires sur ces manuels

Pas de commentaire