Toho-electronics TTM200 Manuel d'utilisateur Page 209

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 264
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 208
48-7009-E 6-61
Setting example: When AT start is assigned to DI 1 (close active)
Set dIF to 0005 and dIP to 0000.
When DI is inactive
200
200
200
At
Switch OFF
DI1
Lighting
When DI is active
Switch ON
Usable DIs for each product model
DIs indicated in the table are usable when DI types are optionally designated.
TTM-204
TTM-205
TTM-209
TTM-207
DI1
DI2
DI3
DI4
DI polarity setting
SEt13
dI
Setting content
Initial value
2
dIP
****
||||
|||+-- DI 1 setting (settable when an option existent)
||+--- DI 2 setting (settable when an option existent)
|+---- DI 3 setting (settable when an option existent)
+----- DI 4 setting (settable when an option existent)
0000
0
Close active
1
Open active
Close active or open active is set for DI function setting described above.
Close active: DI is active when short (max. 333 ) is established between DI terminals.
Open active: DI is active when release (min. 500 k) is established between DI terminals.
Vue de la page 208
1 2 ... 204 205 206 207 208 209 210 211 212 213 214 ... 263 264

Commentaires sur ces manuels

Pas de commentaire