48-7009-E 6-33
<Forward operation>
Off-point CP1 = 0
C1
ON
OFF
PV
Low
SV
High
Off-point CP1 = positive value
CP1
C1
ON
OFF
C point
PV
Low
SV
High
Off-point CP1 = negative value
C1
CP1
ON
OFF
D point
PV
Low
SV
High
C1: Sensitivity setting
C1: Sensitivity setting
CP1: Off-point position
C point: SV + CP1
C1: Sensitivity setting
CP1: Off-point position
D point: SV - CP1
Primary control protection timer
SEt04
CNt
Setting content
Initial value
36
Fdt1
0 to 99 (minutes)
0
37
Ndt1
Main Control Protection on Timer 0~99(min.) 3
0
BEHAVIOR DURING THE SETTING OF MAIN CONTROL PROTECTION OFF TIMER
Setting value
Temperature
Control
output
Control
sensitivity
ON
OFF
Protection
timer