48-7009-E 6-80
6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
■Bank Automatic Switching Function Selection
Bank Automatic Switching Function Selection 3
Bank Auto-Switching Operation OFF
Bank Auto-Switching Operation ON
※In case the “Bank Auto-Switching Operation
ON” is set;
・The Bank Switching Setting with the FUNC
Key will be invalid.
・The Bank Switching Setting by DI will be
invalid.
▲▼ key operation will not be possible either.
※When SET04 bANKH=0, the setting will be
invalid.
There will be no indication either.
※1 Bank Automatic Switching Function Selection (bAF)
This is to set the Bank Automatic Switching ON/OFF. When ON, the bank will be switched
automatically with the selected input by the Bank Automatic Switching Source Setting (bAS).
Setting Range:When 0: Bank Automatic Switching Operation OFF
When 1: Bank Automatic Switching Operation ON
■Behavior Diagram when Bank Automatic Switching is ON
BANK1
RMP
10
P1
4.0
・
・
・
I
20
D
5
BANK2
RMP
10
・
・
・
BANK3
RMP
10
・
・
・
BANK4
RMP
10
・
・
・
BANK5
RMP
5
・
・
・
BANK6
RMP
5
・
・
・
BANK7
RMP
10
・
・
・
BANK0
RMP
P1
3.0
MAX. 16 parameter
・
・
・
I
0
D
0
SV
P1
2.0
I
10
D
2
P1
4.0
I
20
D
5
P1
4.0
I
20
D
5
P1
4.0
I
20
D
5
P1
4.0
I
20
D
5
P1
2.0
I
10
D
2
SET20
setting
Refer
BANK0
BANK1
BANK2
BANK3
BANK4
BANK5
BANK6
BANK7
PM1
PM2
PM3
PM4
PM5
PM6
PM7
SLH
SLL
SLL≦
<PM1
SV
value
PM1≦
<PM2
PM2≦
<PM3
PM3≦
<PM4
PM4≦
<PM5
PM5≦
<PM6
PM6≦
<PM7
PM7≦
<SLH
Bank Automatic Switching.
Switch the bank in accordance with
the source(SV)..
MAX. 8BANK
①
②
③
④
⑤
④
①
③
① 10℃
PM*
setting
PM1
PM2
PM3
PM4
PM5
PM6
PM7
SLL
SLH
20℃
0℃
40℃
60℃
90℃
120℃
140℃
160℃
200℃
② 35℃
Bank 0
Bank 1
Bank 2
Bank 3
Bank 4
Bank 5
Bank 6
Bank 7
③ 70℃
④ 100℃
⑤ 150℃
Auto-Switching
sorce
Bank No.
8BANK(All Threshold*Setting <PM1 to PM7)>)
Bank 7
Zone
Threshold
Setting
NOTE: When the Bank Automatic Switching Function is (SET23 bAF = 1), please note the following points in
case the parameters “SV, SLL, SLH” is set at SET 20 (Bank);
・The value of the “SV, SLL, SLH” set at the Bank will be invalid.
・The Bank registration of “SV, SLL, SLH” will be erased and will go back to the default value.
If (SET 23 bAF = 0) again, the bank registration of “SV, SLL, SLH” are erased, so there is a need to reset.