Toho-electronics TTM200 Manuel d'utilisateur Page 176

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 264
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 175
48-7009-E 6-28
Primary control loop anomaly PV change threshold
SEt04
CNt
Setting content
Initial value
31
PS1
Thermocouple/resistance temperature detector input
0.0 to 999.9 (°C)0 to 999 (°C)
Applicable only for time judgment when PS 1 = 0 (LoP1)
0
Voltage/current input
0 to 9999 (digit)
Applicable only for time judgment when PS 1 = 0 (LoP1)
Set the primary control loop anomaly PV change threshold.
The function is to detect an abnormality in the control loop.
When the time satisfying threshold of TS1 or MS1 exceeds LOP1, the loop abnormality is determined as
detected.
For details, see section Loop abnormality function on pages 5-38 and 39.
- The control loop anomaly PV change threshold is judged at each LoP1 time.
- A loop abnormality is determined if each change threshold is judged to be equal to or below PS1.
- When [PS1 = 0] is true, only time judgment is executed using LOP1.
When the time satisfying threshold of TS1 or MS1 exceeds LOP1, the loop abnormality is determined as detected.
SV
PV
(PS1)
(LoP1)
Vue de la page 175
1 2 ... 171 172 173 174 175 176 177 178 179 180 181 ... 263 264

Commentaires sur ces manuels

Pas de commentaire