Toho-electronics TTM200 Manuel d'utilisateur Page 211

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 264
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 210
48-7009-E 6-63
Start SV permissible range setting
SEt14
tIME1
to
SEt16
tIME3
Setting content
Initial value
3
tSV1
to
tSV3
Thermocouple/resistance temperature detector input
0.0 to 999.9 (C)
0 to 999 (C)
0
Voltage/current input
0 to 9999 (digit)
When the SV start is set, it is set that at what temperature range (°C) the timer should start.
The permissible range is determined in the range of tSV with SV in the center as shown below.
When tSV is set to 1.0°C, the timer operates when the temperature falls within SV ± 0.5°C.
SV
tSV
Note When the ramp action is used together, tSV is set to target SV value.
ON delay timer/OFF delay timer/repeat count setting
SEt14
tIME1
to
SEt16
tIME3
Setting content
Initial value
4
oNt1
to
oNt3
0:00 to 99:59 (hour: minute or minute: second)
0:00
5
oFt1
to
oFt3
0:00 to 99:59 (hour: minute or minute: second)
0:00
6
RUN1
To
RUN3
0 to 99 counts (0 for unlimited counts)
1
Set the ON delay timer, OFF delay timer and repeat count setting of timers.
Use oNt 1 to 3 for setting the ON delay timer time of timers 1 to 3.
Use oFt 1 to 3 for setting the OFF delay timer time of timers 1 to 3.
Use RUN 1 to 3 for setting the repeat count of timers 1 to 3.
Note When the function setting of tMF 1 to 3 is set for the SV start, the ON delay timer screen is not displayed.
For the details on Timer Setting, please refer to Operation Manual Timer (P5 31 to 37).