48-7009-E 7-33
7.5.17 Bank automatic switching function setting mode (SET 23)
Setting data
Character
Setting (monitor) value
Initial value
Unit
Setting
value
Blind
Bank automatic
switching function
selection
bAF
0: Bank automatic switching run
OFF
1: Bank automatic switching run
ON
* With Bank automatic switching
run ON setting:
- Bank switching setting by using
the FUNC key is ineffective.
- Bank switching setting by using
DI is ineffective.
/ key operation is not also
allowed.
* When SET 04 bANKH 0, the
setting is neither effective nor
displayed.
0
None
Bank automatic
switching source
setting
bAS
Function:
*0: Selects a SV value.
*1: Selects a ramp SV value.
*2: Selects a PV value.
Control mode interlock function:
0*: All modes
1*: Only RUN/MAN mode
2*: Only RUN mode
* Selects a source for the SV
value for performing auto bank
switching.
* When SET 04 bANKH 0, the
setting is neither effective nor
displayed.
0.0
None
Zone threshold
setting
PM*
SLL to SLH
* Sets a threshold for bank
automatic switching of [* 1 to
7] (example of 8 banks).
* When SET 04 bANKH 0, the
setting is neither effective nor
displayed.
1200
C
Digit
Zone threshold
sensitivity range
setting
ASC
During temperature input
0 to 999 (0.0 to 999.9) (C)
During analog input
0 to 9999 (digit)
* Sets a sensitivity setting for a
threshold for performing bank
automatic switching.
None is displayed if bAF 0
(OFF) and bAS *0 or *1 and
SET 02 LR 0.
* When SET 04 bANKH 0, the
setting is neither effective nor
displayed.
0
C
Digit
Note SET 23 is selectable only on Ver3.xx or later.