Control mode
SEt04
CNt
Setting content
Initial value
6
Md
RUN
Control start
RUN
MAN
Manual
RdY
Control stop
tIME1
Timer 1 operation
tIME2
Timer 2 operation
tIME3
Timer 3 operation
Set the control mode.
Control stop (RdY): Primary/secondary operating amount limiter lower limit is output.
Control start (RUN): Normal control is executed.
Manual (MAN): Operating amount set in the primary/secondary operating amount is output.
Timer interlocking control (tIME 1 to 3): A control where the normal control and timer operation are interlocked is executed.
For start (RUN)/stop (RdY)/manual (MAN) of control, see section 5.4.3 Mode/manual function on page 5-28.
For timer interlocking control (tIME 1 to 3), see section 5.4.5 Timer function on pages 5-32 to 37.
Control type setting
SEt04
CNt
Setting content
Initial value
7
CNt
0
Primary --- None
Secondary --- None
1
1
Primary --- PID control
Secondary --- None
2
Primary --- ONOFF control
Secondary --- None
3
Primary --- PID control
Secondary --- PID control
4
Primary --- PID control
Secondary --- ONOFF control
5
Primary --- ONOFF control
Secondary --- ONOFF control
6
Primary --- position proportional
Secondary --- position proportional
Set the control type (method).
Control types of primary and secondary control outputs that are set on this equipment can be assigned to the methods of 0 to 6.
For the content of the assignment, see the setting content listed above.
Note
(1) In case that the control type is set to 3 (primary/secondary PID control) and the tuning type to 3, 4 or 5, take care that the tuning
type changes to 1 (primary tuning) in conjunction with the change of the control type.
(2) Take care that the position proportional control (CNt: 6) is selectable even when the primary/secondary control output is not set
for the target connection setting.
PID control type/type B mode
SEt04
CNt
Setting content
Initial value
8
tYP
0
type A (normal PID control)
1
1
type B (overshoot suppression function)
2
type C (disturbance suppression function)
9
bMd
0
Overshoot suppression --- moderate
1
1
Overshoot suppression --- intermediate
2
Overshoot suppression --- intense
Set the PID control type.
For the use of the equipment in setting of the control type to be the PID control, a selection can be made among three control types of
0 (type A) to 2 (type C), whichever is best suited for the application.
Note The type B mode can be set when the PID control type is set to 1 (type B). In the type B mode, a result from integration (I) or
differentiation (d) of the auto-tuning is multiplied by a coefficient. The intermediate type is same value as it is. The type C
(disturbance suppression function) cannot be set when the self-tuning is set in the tuning type setting.
For control characteristics of each control type, see section 5.4.1 Auto-tuning (AT) function on pages 5-23 to 25.