Output 1 and 2 transmission scaling upper limit/lower limit setting
SEt05
oUt1
to
SEt06
oUt2
Setting content
Initial value
12
tRH1
to
tRH2
Thermocouple/resistance temperature detector input
tRL* to 2999.9 (C)
tRL* to 2999 (C)
1200
Voltage/current input
tRL* to 29999 (digit)
12000
13
tRL1
to
tRL2
Thermocouple/resistance temperature detector input
-1999.9 to tRH* (C)
-1999 to tRH* (C)
0
Voltage/current input
-19999 to tRH* (digit)
Set the transmission scaling upper limit/lower limit of the transmission output.
The output 1 or output 2 being set for analog output can be used as a transmission output.
For using the output 1 or 2 as a transmission output, set 17 (transmission output) for the target connection of the output 1 or 2.
This function is to scale the transmission output range with respect to the measurement/setting value.
The decimal point position is set in conjunction with the decimal point position setting (dP 1).
Note This function cannot be set when 3 or 4 (primary/secondary control operating amount) is set in the transmission output
function setting.
Example: When transmitted in the following setting
Output 1
Output 2
Output type
Current 4 - 20 mADC
Current 4 - 20 mADC
Output target connection setting
o1F=17
o2F=17
Transmission output function setting
tRN1=01
tRN2=11
Transmission scaling upper limit
tRH1=1200.0
tRH2=1200.0
Transmission scaling lower limit
tRL1=0.0
tRL2=0.0
0
20
0
1200
PV transmission (forward operation)
PV transmission (reverse operation)
Output current [mA]
PV [C]
4