48-7009-E 6-56
■ Output 1 and 2 transmission scaling upper limit/lower limit setting
Thermocouple/resistance temperature detector input
tRL* to 2999.9 (C)
tRL* to 2999 (C)
Voltage/current input
tRL* to 29999 (digit)
Thermocouple/resistance temperature detector input
-1999.9 to tRH* (C)
-1999 to tRH* (C)
Voltage/current input
-19999 to tRH* (digit)
Set the transmission scaling upper limit/lower limit of the transmission output.
The output 1 or output 2 being set for analog output can be used as a transmission output.
For using the output 1 or 2 as a transmission output, set 17 (transmission output) for the target connection of the output 1 or 2.
This function is to scale the transmission output range with respect to the measurement/setting value.
The decimal point position is set in conjunction with the decimal point position setting (dP 1).
Note This function cannot be set when “3” or “4” (primary/secondary control operating amount) is set in the transmission output
function setting.
Example: When transmitted in the following setting
Output target connection setting
Transmission output function setting
Transmission scaling upper limit
Transmission scaling lower limit
PV transmission (forward operation)
PV transmission (reverse operation)