48-7009-E 6-2
6.1 Input 1 type setting
■ Input 1 type setting
Press the MODE key for making a setting effective (including reverse feed).
See the input 1 type setting table.
Set the input type of the input 1.
The input 1 is for a multi-input for thermocouple, resistance temperature detector, voltage and current. Set according to the
input being used.
Input 1 type setting table
Measurement/
setting range
Either larger ± (0.3 % + 1 digit) or ± 2°C
Note: ± 3°C for - 100.0 to 0.0°C and ± 4°C for
- 200.0 to - 100.0°C
No specification for 400°C or lower for B
thermocouple
Either larger ± (0.3 % + 1 digit) or ± 4°C
± 6°C for lower than 0°C
Either larger ± (0.6 % + 1 digit) or ± 4°C
± 9.4°C 1 digit
No specification on accuracy for lower than
800°C
Either larger ± (0.3 % + 1 digit) or ± 2°C
Either larger ± (0.3 % + 1 digit) or ± 0.9°C
-19999 to +29999
Display resolution to be
20000 or less
*1
Random
change of
decimal point
position
allowed
±0.5 % ±1 digit of full scale
±0.3 % ±1 digit of full scale
*1 The display range of analog input is min. - 19999 digits and max. +29999 digits. The range, however, can be narrowed by
setting the scaling upper limit (FSH 1) and lower limit (FSL 1) settings. See below for the narrowed display range.
<Where input is 0 - 10 mV/0 - 1 V/0 - 5 V/0 - 10V>
• Display of the lower limit side: Up to - 2 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale
<Where input is 1 - 5 V/4 - 20 mA>
• Display of the lower limit side: Up to - 12 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale
Full scale is defined as the range from FSL 1 to FSH 1.
The display range for temperature input (setting Nos. of 0 to 12 in the table above) is fixed.