48-7009-E 6-55
Output 1 and 2 transmission output function setting
SEt05
oUt1
to
SEt06
oUt2
Setting content
Initial value
11
tRN1
tRN2
Transmission content selection
tRN1=01
tRN2=01
*1
PV (measurement value) output
*2
SV (setting value) output
*3
MV 1 (primary control operating amount) output
*4
MV 2 (secondary control operating amount) output
*5
Control SV (Setting Value) output 3
Forward/reverse operation selection
0*
Forward operation
1*
Reverse operation
Set the output content of transmission output.
The output 1 or output 2 being set for analog output can be used as a transmission output.
For using the output 1 or 2 as a transmission output, set 17 (transmission output) for the target connection of the output 1 or 2.
The transmission output is a function that delivers power of the conditions of the measurement value (PV), setting value (SV),
primary control operating amount (MV 1) , secondary control amount (MV 2) and the control SV (SV Setting Value ) output
with either the voltage or current signal (designated by model assignment upon order).
Also, by setting the movement to either forward or reverse, the voltage or current signal can also be made to move forward or
reverse.
Example: When transmitted in the following setting
Output 1
Output 2
Output type
Current 4 - 20 mADC
Current 4 - 20 mADC
Output target connection setting
o1F=17
o2F=17
Transmission output function setting
tRN1=03
tRN2=13
0
20
-10%
100%
MV transmission (forward operation)
MV transmission (reverse operation)
Output current [mA]
Operating amount [%]