48-7009-E 5-51
*4: Time unit setting (H/MP)
Set time unit and step transfer condition (time countdown condition) of a step.
Setting range Initial value: 0: Step time (hour: minute)
0: Step time (hour: minute)
1: Soak time 1 (hour: minute)
2: Soak time 2 (hour: minute)
3: Step time (minute: second)
4: Soak time 1 (minute: second)
5: Soak time 2 (minute: second)
Note Regarding meanings of step, soak 1 and soak 2
Step time: The step proceeds in accordance with a set step time (SET 22 tIM*) regardless
statuses of PV or SV. Therefore, a step proceeds to the next one when set time
elapses.
Soak time 1: Time is count down if a PV falls within the set WAIT range even once. A step
proceeds to the next one when set time elapses. Judgment is made with a set PV
even if a ramp is set.
Soak time 2: Time is count down only within a set WAIT range.
For details, see Complementary explanation of the program run in Section 5.5.7 (P5-61 and 62).
*5: WAIT range setting (WAIt)
Set range for a PV value when using the soak time 1 or 2 function.
Setting range Initial value: 2
(During temperature input)
Soak time 1: 0 to 999 (0.0 to 999.9)C
Soak time 2: 0 to 999 (0.0 to 999.9)C
(During analog input)
Soak time 1: 0 to 9999 (digit)
Soak time 2: 0 to 9999 (digit)
Note Complementary to the WAIT range setting
The operation for the soak time 2 (H/MP 2) is the same as that for the soak time 1 in the WAIT
range setting (WAIt 0).
For details, see Complementary explanation of the program run in Section 5.5.7 (P5-61 and 62).