48-7009-E 6-3
Input 1 connection table
Note Switchover of the input types may result in change of each setting value due to limits being applied, such as SLH, SLL,
tRH and tRL.
■ Display scaling upper limit/lower limit setting
Voltage/current input only
FSL 1 to 29999 (digit)
Voltage/current input only
-19999 to FSH 1 (digit)
Display scaling upper limit/lower limit are set for the input 1.
This setting is possible only when the input 1 is set for voltage/current input.
Setting example: Where the input type is the 4 - 20 mA setting and the display range is 0.0 digit for 4 mA and 100.0 digits
for 20 mA.
Set as INP 1: 20, FSH 1: 100.0, FSL 1: 0.0 and dP 1: 0.0.
* For this setting, the display range is - 12.0 to 112.0.
For -12.0 or smaller, the display is “underscale display.”
For 112.0 or larger, the display is “overscale display.”
Note
(1) Display resolution is 20,000 or less.
Take care it when the range from FSL 1 to FSH 1 is set larger than 20,000.
Setting example: Fluctuation or missing value of PV may be caused when the input 1 is set to the input type of 4 - 20 mA,
FSL 1 to -19999 digits and FSH 1 to 29999 digits.
(2) Take care that setting values for FSH 1 and FSL 1 can be the same.