Toho-electronics TTM200 Manuel d'utilisateur Page 171

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 264
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 170
48-7009-E 6-23
Primary control operating amount change limiter ascent setting
SEt04
CNt
Setting content
Initial value
24
oU1
0.0 to 549.9 (%)
Function turned off at 0.0 (%) setting
0.0
Set the primary control operating amount change limiter ascent.
A limit is set to the ascent percentage of the operating amount change calculated.
An operating amount allowed with ascent for a second is set in the unit of percentage.
Calculated
operating amount
Limited operating
amount
100%
100%
0%
0%
Time
MLL 1 is set for the initial MV at power-on.
Note
(1) The setting is effective also during AT.
(2) When the setting is changed, re-AT is required due to different control result.
(3) The setting value of 100 % allows ascent of only 20 % in the input sampling (200 ms).
In order to have ascent of 100 % in the input sampling (200 ms), set the setting value to 500 %.
(1 s ÷ 200 ms) × 100 % = 500 %
Set the setting value to 0.0 % (OFF) when ascent of 110 % from 0 % in a second is desired for an analog input.
Primary control operating amount change limiter descent setting
SEt04
CNt
Setting content
Initial value
25
od1
0.0 to 549.9 (%)
Function turned off at 0.0 (%) setting
0.0
Set the primary control operating amount change limiter descent.
A limit is set to the descent percentage of the operating amount change calculated.
An operating amount allowed with descent for a second is set in the unit of percentage.
100%
100%
0%
0%
Calculated
operating amount
Limited operating
amount
Time
MLL 1 is set for the initial MV at power-on.
Note
(1) The setting is effective also during AT.
(2) When the setting is changed, re-AT is required due to different control result.
(3) The setting value of 100 % allows descent of only 20 % in the input sampling (200 ms).
In order to have descent of 100 % in the input sampling (200 ms), set the setting value to 500 %.
(1 s ÷ 200 ms) × 100 % = 500 %
Set the setting value to 0.0 % (OFF) when descent of 110 % from 0 % in a second is desired for an analog input.
Vue de la page 170
1 2 ... 166 167 168 169 170 171 172 173 174 175 176 ... 263 264

Commentaires sur ces manuels

Pas de commentaire